Skip to Content
TotFlex
Fire Sprinklers

Concealed Sprinklers

A pendent sprinkler fully recessed above a flat cover plate — invisible in the finished ceiling until heat releases the cover and the head deploys. For interiors where aesthetics matter.

K5.6 (80)K factor12 barWorking pressure57 – 93 °CRatings
Concealed Sprinklers
/01

Technical Data

Product codesSP25 (standard) · SP26 (quick response)
TypeConcealed pendent sprinkler with flat cover plate
ResponseStandard (5 mm bulb) or Quick (3 mm bulb)
K factorK5.6 (80)
Thread½" NPT (15 mm)
Working pressure12 bar (175 psi)
Temperature ratingsSprinkler 57 – 93 °C with matched 57 / 68 °C covers
FinishBrass sprinkler · flat ceiling cover plate
FLUSH CEILINGTWO-STAGEK5.6 (80)
ApplicationsResidencesHotelsHospitalsDormitoriesShopping mallsOffices
/02

Selection Guide

SP25Standard response

5 mm bulb concealed pendent for ordinary-hazard interiors.

Best forStandard interiors
SP26Quick response

3 mm bulb for life-safety occupancies where earlier operation is required.

Best forHotels · hospitals
CoversMatched plates

Cover plates rated 57 or 68 °C, always below the sprinkler rating so the plate drops first.

Best forCorrect staging
Never paint a fitted cover plate — field paint changes its release temperature and voids the listing.
/03

Datasheet & Drawings

Each configuration has its own one-page datasheet with the spray coverage curves — download the variant you are specifying.

Test records and material certificates are supplied with your shipment.

Product datasheet
/05

Frequently Asked Questions

How does a concealed sprinkler operate?

In two stages. Heat first releases the flat cover plate at its rated temperature; the sprinkler drops below the ceiling, and its glass bulb then operates at the sprinkler rating to discharge water.

Why are the cover and sprinkler temperatures paired?

The cover must always release before the sprinkler operates, so covers are rated at or below the sprinkler rating — for example a 68 °C cover with a 79 °C or 93 °C sprinkler. Pairs are supplied matched.

Can the cover plate be painted to match the ceiling?

No. Site-applied paint changes the plate’s thermal response and voids the listing. Factory-finished plates should be specified in the required colour instead.

What is the working pressure rating?

Twelve bar (175 psi), with the standard K5.6 (80) orifice and a half-inch NPT thread.

Where are concealed sprinklers typically used?

Suspended-ceiling interiors where appearance matters — hotels, residences, hospitals, dormitories, offices and retail spaces with concealed pipework.

Engineered to order. Delivered worldwide.

Send your project requirements — hazard class, configurations, response type, temperature ratings and quantities — and our team returns a submittal package and lead time.

Request a quote
Request a quote